copper pipe

ANNEALED COPPER PIPE IN COILS AND RAW COPPER IN RODS FOR AIR CONDITIONING AND REFRIGERATION.

Copper pipe features
ACR copper Cu-DHP CW024A (Cu = 99.90% min., P = 0.0015 ÷ 0.040%) – physical state according to EN 12735-1:2020, annealed in rolls (R220) and raw in rods (R290) – carbon residue <0.34 mg/dm². Tolerances and eccentricities comply with EN 12735-1:2020, and the ends are sealed according to ASTM B280. The inner surface of the tube is particularly shiny, clean, and dry. Internal cleanliness is ensured by sealing the ends of each tube.
Fields of use
  • Split-system systems
  • Large capacity air conditioning systems such as: VRV,
    VRF, Multisplit and Chiller
  • Food refrigeration systems (refrigerated counters, cooling
    coils, drinking water dispensers, ice cream machines…)
  • Other industrial systems

 

Tube external
diameter
Tube thickness
in coils
Tube thickness
in rods
Coils length Rods
length
Operating Pressure of
annealed tube in coils
Operating Pressure of
annealed tube in rods
Available
LWC
mm Inches. mm mm m m mm MPa
6 1 1 50 5 18,70 24,65
6,35 ¼” 0,8 1 1 50 5 14,14 17,67 23,29
9,52 3/8″ 0,8 1 1 50 5 9,42 11,79 15,54
10 1 1 50 5 11,22 14,79
12 1 1 50 5 9,35 12,33
12,70 ½” 0,8 1 1 50 5 7,07 8,83 11,65
14 1 1 50 5 8,01 10,56
15 1 1 50 5 7,48 9,86
15,875 5/8” 1 1 50 5 7,07 9,32
16 1 1 50 5 7,01 9,24
18 1 1 1,5 50 5 6,23 8,22 12,33
19,05 3/4” 1 1 25 5 5,89 7,76
22 1 1,5 1 1,5 25 5 5,10 7,65 6,72 10,08
22,225 7/8” 1 1 25 5 5,05 6,65
25,4 1” 1 1,5 5 5,28 7,92
28 1 1,5 5 5,18
28,575 1”1/8 1 5 5,18
31,75 1”1/4 1 5 4,66 6,99
34,925 1”3/8 1 5 4,23 6,35
35 1 5 4,23 6,34
38,1 1”1/2 1 5 3,88 5,31
41,28 1”5/8 1 5 3,54 5,31
42 1 5 3,52 5,28
54 5 4,11